BAM three phases High voltage Power Capacitor

Short Description:

Altitude: less than 1000m; Ambient Temperature: -40℃ ~ +40℃。
No violent mechanical vibration, no harmful gas and vapor, no electric, and explosive, and explosive dust in location.
Continuous operation voltage: 1.00 Un, long-term max, Over voltage: less.1 Un.
Stable over-curent (including harmonics current) less 1.3 In.

Product Detail

Product Tags

BAM High Voltage Power Capacitor

Application and Standards:

High voltage capacitor is mainly used in the A. C. Power system with 50Hz to improve power factor. The performance sonforms to GB 3083.2-89 《High voltage shunt capacitor》and IEC60871-1987.

GB/T11024-2010 National standard 《Rated voltage 1kV or above shunt capacitors for AC power systems

JB/7112-2000 Machinery Industry standard 《Assembled HV Shunt Capacitor

DL/T628-1997 Electric Power Industry standard 《Assembled HV Shunt Capacitor Ordering Technical Requirement》

Usage Conditions:

1.Altitude: less than 1000m; Ambient Temperature: -40℃ ~ +40℃.

2.No violent mechanical vibration, no harmful gas and vapor, no electric, and explosive, and explosive dust in location.

3.Continuous operation voltage: 1.00 Un, long-term max, Over voltage: less.1 Un.

4.Stable over-curent (including harmonics current) less 1.3 In.

5.With stand voltage: between terminal 2.15, time rated voltage for 10 seconds, between terminals and container 42kV for 10 seconds.

Main technical characteristics:

1.Rated voltage: 6.3kV, 6.6kV, 6.6/√3kV, 7.96kV, 10.5kV, 11kV, 11kV, 11/√3kV, please indicated in the order if you want the other special capacity.

2.Rated capacity: 33~334kvar please indicated in the order if you want the other special capacity.

3.Capacity tolerance: -5 ~ 15%.

4.Loss angel tangential value: film & papaer medium tg θ≦0.08%,film medium tg θ≦0.05%.

5.Withstand voltage: it can afford AC2.15 or DC4.3 times rated voltage between the capacity pales, last about 10s without break or flash, BIL: 6kV(30kV), 10kV(42Kv).

6.Free discharge: it has the inner resistance,10min after cutting off the power supply, the residual voltage will reduce to 75V from √2 Un.

7.Max. Current: running smoothly under the 1.3 time rated voltage, over voltage, capacity positive tolerance and harmonic wave which can not exceed 1 min each 24 hours.

8.Max.Current: running smoothly under the 1.3 time rated voltage, over voltage, capacity positive tolerance and harmonic wave which can not 1.43 time rated current.

9.Standard: GB/T 112024.1-2001, IEC6087:1997.

tr

SEPERATE PHASE POWER CAPACITOR

Model
BAM
Rated Voltage
(kV)
Rated Output (kVAr) Rated Capacitance(uF)  Rated Current In(A)
6.3-25-1W 6.3 25 2.006 3.968
6.3-30-1W 6.3 30 2.406 4.762
6.6/√3-25-1W 6.6/√3 25 5.481 6.561
6.3/√3-30-1W 6.6/√3 30 6.577 7.873
6.3/√3-50-1W 6.6/√3 50 10.96 13.12
10.5-25-1W 10.5 25 0.722 2.38
10.5-30-1W 10.5 30 0.886 2.857
10.5-50-1W 10.5 50 1.444 4.762
11/√3-30-1W 11/√3 30 2.368 4.724
11/√3-50-1W 11/√3 50 3.946 7.873
6.3-30-1W 6.3 30 2.4 4.76
6.3-50-1W 6.3 50 4 7.9
6.3-100-1W 6.3 100 8 15.9
6.3-200-1W 6.3 200 16 31.7
6.3-300-1W 6.3 300 twenty four 47.6
6.3-334-1W 6.3 334 26.8 53
10.5-50-1W 10.5 50 1.44 4.8
10.5-100-1W 10.5 100 2.9 9.5
10.5-150-1W 10.5 150 4.3 14.3
10.5-200-1W 10.5 200 5.8 19
10.5-300-1W 10.5 300 8.67 28.6
10.5-334-1W 10.5 334 9.65 31.8
11/√3-50-1W 11/√3 50 3.95 7.87
11/√3-100-1W 11/√3 100 7.89 15.75
11/√3-150-1W 11/√3 150 11.84 23.6
11/√3-200-1W 11/√3 200 15.78 31.5
11/√3-300-1W 11/√3 300 23.68 47.2
11/√3-334-1W 11/√3 334 26.36 52.6
6.6/√3-50-1W 6.6/√3 50 10.96 13.12
6.6/√3-100-1W 6.6/√3 100 21.9 26.24
6.6/√3-150-1W 6.6/√3 150 32.9 39.36
6.6/√3-200-1W 6.6/√3 200 43.8 52.48
6.6/√3-300-1W 6.6/√3 300 65.8 78.7
6.6/√3-334-1W 6.6/√3 334 73.2 87.6
11-100-1W 11 100 2.63 9.1
11-150-1W 11 150 3.95 13.6
11-200-1W 11 200 5.26 18.2
11-300-1W 11 300 7.89 27.3
11-334-1W 11 334 8.79 30.4
12-100-1W 12 100 2.2 8.33
12-150-1W 12 150 3.3 12.5
12-200-1W 12 200 4.4 16.7
12-300-1W 12 300 6.64 25
12-334-1W 12 334 7.39 27.8
12/√3-100-1W 12/√3 100 6.63 14.4
12/√3-150-1W 12/√3 150 9.95 21.7
12/√3-200-1W 12/√3 200 13.3 28.9
12/√3-300-1W 12/√3 300 19.9 43.3
12/√3-334-1W 12/√3 334 22.1 48.2
12/√3-400-1W 12/√3 400 26.54 57.74
6.3-100-1W 6.3 100 8 15.9
6.3-150-1W 6.3 150 12 23.8
6.3-200-1W 6.3 200 16 31.7
6.3-300-1W 6.3 300 twenty four 47.6
6.3-334-1W 6.3 334 26.8 53
6.6-100-1W 6.6 100 7.3 15.2
6.6-150-1W 6.6 150 11 22.7
6.6-200-1W 6.6 200 14.6 30.3
6.6-300-1W 6.6 300 twenty two 45.5
6.6-334-1W 6.6 334 24.4 50.6
6.6/√3-100-1W 6.6/√3 100 21.9 26.24
6.6/√3-150-1W 6.6/√3 150 32.9 39.36
6.6/√3-200-1W 6.6/√3 200 43.8 52.48
6.6/√3-300-1W 6.6/√3 300 65.8 78.7
6.6/√3-334-1W 6.6/√3 334 73.2 87.6
11/√3-100-1W 11/√3 100 7.89 15.75
11/√3-150-1W 11/√3 150 11.84 23.6
11/√3-200-1W 11/√3 200 15.78 31.5
11/√3-300-1W 11/√3 300 23.68 47.2
11/√3-334-1W 11/√3 334 26.36 52.6
11-100-1W 11 100 2.63 5.25
11-150-1W 11 150 3.95 7.87
11-200-1W 11 200 5.26 10.5
11-300-1W 11 300 7.9 15.75
11-100-1W 11 100 2.63 5.25
11-150-1W 11 150 3.95 7.87
11-200-1W 11 200 5.26 10.5
11-300-1W 11 300 7.9 15.75
12-100-1W 12 100 2.2 4.8
12-150-1W 12 150 3.3 7.2
12-200-1W 12 200 4.4 9.6
12-300-1W 12 300 6.64 14.45
12-100-1W 12 100 2.2 4.8
12-150-1W 12 150 3.2 7.2
12-200-1W 12 200 4.4 9.6
12-300-1W 12 300 6.64 14.45
11/√3-200-1W 11/√3 200 15.78 31.5
11/√3-334-1W 11/√3 334 26.36 52.6
12/√3-200-1W 12/√3 200 13.3 28.9
12/√3-334-1W 12/√3 334 22.1 48.2
12-200-1W 12 200 4.4 16.7
12-334-1W 12 334 7.39 27.8
10.5-200-1W 10.5 200 5.8 19
10.5-334-1W 10.5 334 9.65 31.8