GRM6-40.5 Series Cubicle Type Gas Insulated Switchgear

Short Description:


Product Detail

Product Tags

Product Overview

GRM6-40.5 Series are a new type SF6 gas-insulated compact switchgears. Circuit breakers, disconnectors, and other parts are enclosed in 3mm-thick metal containers filled with a low-pressure SF6 gas. Thus, the equipment is compact, reliable, and safe; free of environmental impacts, free maintenance and long service life, etc.

GRM6-40.5 Series switchgears are suitable for control, protection and monitoring of 40.5 kV, three-phase, single busbar electrical system, widely used in generating companies, mining, etc.

 

Applicable Standars

IEC 62271-1:High-voltage switchgear and controlgear-Part 1: Common specifications

IEC 62271-100 :High-voltage switchgear and controlgear–Part 100: Alternating-current circuit-breakers

IEC 62271-102 High-voltage switchgear and controlgear–Part 102: Alternating current disconnectors and earthing switches

IEC 62271-103 High-voltage switchgear and controlgear–Part 103: Switches for rated voltages above 1 kV and up to and including 52 kV

IEC 62271-105 High-voltage switchgear and controlgear–Part 105: Alternating current switch-fuse combinations

IEC 62271-200:High-voltage switchgear and controlgear–Part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1kV and up to and including 52 kV

IEC 60044-2:Instrument transformers–Part 2: Inductive voltage transformers

IEC 60044-1:Instrument transformers–Part 1:Current transformers

 

Use Conditions

Altitude: ≤4000m★

Ambient air temperature: -25℃~+40℃;

Relative air humidity: daily average ≤95%, monthly average ≤90%;

Seismic intensity ≤8 class;

Places free from fire, explosion, serious contamination, chemical corrosion and severe vibration.

Note★: The manufacturer must be consulted in advance if site altitude is over 1000 m so as to adjust the inflation pressure.

Model number definition

Model explanation

 

 

Main Technical Parameters

No.

Descriptions

Unit

Value

1

Rated voltage

kV

40.5

2

Rated frequency

Hz

50

3

Rated continuous current

A

1250, 2500

4

Rated

insulation

level (Out,

Up, )

Power

frequency

withstand

voltage(Out)

(1min)

Between phase and phase to earth

kV

95

Across the isolating distance

kV

118

Auxiliary and control circuits (Ua)

kV

2

Lightning

impulse

withstand

voltage (Up)

Between phase and phase to earth

kV

185

Across the isolating distance

kV

215

5

Rated short-time withstand current (Ik/tk)

kA/s

25/4, 31.5/4

6

Rated peak withstand current (Ip)

kA

63, 80

7

Rated short-circuit breaking current (Isc)

kA

25, 31.5

8

Rated short-circuit making current

kA

63, 80

9

Circuit breaker electrical endurance

/

30 times

10

Rated operating sequence.

/

O-0.3s-CO-180s-CO

11

Mechanical endurance

Circuit breaker

Ops

20000

Disconnectors/Earthing switches

Ops

5000

12

Resistance of the circuit

1250A

≤120

2500A

≤80

13

Rated gas- filled pressure (the pressure at 20 °C)

MPa

0.02

14

Annual leakage rate (relative pressure)

/

≤0.01%

15

Isolation medium

/

SF6

16

 

Degree of protection

(IP)

Isolation medium

/

IP2XC

Gas tank

/

IP67

Enclosure

/

IP41

Enclosure

/

IK10

17

Classification IAC and Internal IAC

/

A-FLR , 31.5 kA 1s

 

Outline dimension

DIMENSION

 