ZW32 outdoor pole mounted auto recloser

Short Description:


Product Detail

Product Tags

Description

ZW32 Auto recloser is a special type of electrical circuit breaker that is designed to rapidly open and close. Unlike circuit breakers, which are designed to “trip” and stay in the open state, it can rapidly transition states from closed, to open and back. These devices aim to stop network faults from causing long outages, by quickly restoring power.

Auto recloser is the automatic configuration of a circuit breaker to close after opening due to a protection operation. It is used in both Medium Voltage distribution and High Voltage Transmission, although in slightly different ways. Distribution VCB uses standalone auto reclosers, such as the Recloser product, which has an integrated control system, an HV Reclosing Circuit Breaker and a Remote SCADA FTU.

 It is a long mechanical life vacuum switch that provides an operational life of over 100,000 (30,000 open / close) maintenance-free operations. Use our auto recloser ZW32 will result in substantial savings from reduced maintenance and maximized bank uptime and will also improve power quality. It complies with standards ANSIC37.66 and China standard. The rated voltage ranges 33KV 35KV 36KV 40.5KV. It has motorized spring type & magnetic actuator (with control box) type.

◆ Use Conditions

1.Ambient temperature: -30℃~+60℃;

2.Altitude: ≤3000m;

3.Wind speed: ≤34m/s;

4.Pollution grade: ≤IV.

5.Storage temperature: -40℃~+85℃.

◆ Main Technical Parameters

NO. Items Unit Value
1 rated voltage kV 40.5
2 1min power frequency withstand voltage kV 95
3 lightning impulse withstand voltage kV 185
4 rated frequency Hz 50
5 rated current A 630,1250,1600
6 rated short circuit breaking current kA 20, 25, 31.5
7 rated short circuit making current (peak)
kA 50, 63, 80
8 rated peak withstand current kA 50, 63, 80
9 4s withstand current kA 20, 25, 31.5
10 rated operating sequence S O-0.1s-CO-3s-CO-6S-60s recovery
11 rated short circuit current breaking number times 30
12 mechanical life times 10000
13 mechanism control voltage IN AC/DC220
14 secondary circuit 1min power frequency withstand voltage kV 2
15 clearance distance between open contacts mm 16±1
16 over travel mm 4±0.5
17 opening speed m/s 1.4-1.8
18 closing speed m/s 0.4-0.8
19 contact closing bounce time ms ≤5
20 three phase opening/closing asynchronism ms ≤2
twenty one closing time ms ≤100
twenty two opening time ms ≤50
twenty three weight kg 270