Main Technical Parameters
Model

CKG4-160-630/12-5

Main circuit rated voltage (KV)

12

12

12

12

Main circuit rated current (A)

160

250

400

630

Main circuit making ability (A/100 Ops.)

1600

2500

4000

6300
Main circuit break-making ability (A/25 Ops.)

1280

2000

3200

5000
Maximum break ability (A/3 Ops.)

3200

3200

4000

6300
Mechanical life (Ops.)

1000000

1000000

1000000

1000000

Power-frequency withstand voltage for main circuit (kV)

42

42

42

42

Power-frequency withstand voltage for ouxillary circuit (kV)

2.5

2.5

2.5

2.5

Power-frequency withstand voltage for control circuit (kV)

2

2

2

2

Rated operating frequency (Ops./h)

300

300

300

300

Opening time (ms)

≤120

≤120

≤120 ≤120
Closing time (ms)

≤150

≤150

≤150

≤150
Clearance between open contact (mm)

5±0.5

5±0.5

5±0.5

5±0.5
Over travel (mm)

≥1.2

≥1.2

≥1.2

≥1.2