Main Technical Parameters
Model | Rated voltage (V) | Rated current main circuit (A) | Main contact Parameters | Power frequency voltage resistance V (effective value) | |||||
Main circuit | Control circuit | Distance (mm) | Overtravel (mm) | Final pressure (N) | Main circuit | Auxiliary circuit | control circuit | ||
JCZ5-7.2D(J)/160 | 7200 | 100, 220 | 160 | 4.5±0.5 | 1.5 ±0.5 | >85N | 32000 | 2500 | 2000 |
JCZ5-7.2D(J)/250 | 7200 | 100, 220 | 250 | 4.5±0.5 | 1.5 ±0.5 | >85N | 32000 | 2500 | 2000 |
JCZ5-7.2D(J)/400 | 7200 | 100, 220 | 400 | 4.5±0.5 | 1.5 ±0.5 | >85N | 32000 | 2500 | 2000 |
JCZ5-7.2D(J)/630 | 7200 | 100, 220 | 630 | 5±0.5 | 1.5±0.5 | >85N | 32000 | 2500 | 2000 |
Model | Making capacity | Breaking capacity | Limit breaking current (A) | Electricity life times | Weight (Kg) | ||||
JCZ5-7.2D(J)/160 | 10le, 100times | 8le, 25times | 10le | 30×104 | 28 | ||||
JCZ5-7.2D(J)/250 | 10le, 100times | 8le, 25times | 10le | 30×104 | 28 | ||||
JCZ5-7.2D(J)/400 | 10le, 100times | 8le, 25times | 10le | 30×104 | 28 | ||||
JCZ5-7.2D(J)/630 | 10le, 100times | 8le, 25times | 10le | 130×104 | 28 |
Note: le means main circuit rated current
Outline and Installation Dimensions