ZN85-40.5 indoor HV vacuum circuit breaker is a 3-phase AC 50Hz 40.5kV indoor switch equipment.
♦ Installation way: withdrawable type;
♦ Operating mechanism: spring operating mechanism;
♦ Pole type: assembled pole, embedded pole;
♦ Application: switchgear KYN61-40.5.
♦ Secondary plug: 58pins, 64pins.
Environmental Conditions
♦ Ambient temperature: -15r~+40r;
♦ Altitude:
♦ Relative humidity: daily average ;
♦ Earthquake intensity:
♦ Places without fire, explosion hazard, serious filthy, chemical corrosion, as well as intense vibration.
Main Technical Parameters
No | Item | Unit | Value |
1 | Rated voltage | kV | 40.5 |
2 | Rated current | A | 1250 1600, 2000, 2500 |
3 | Rated short circuit breaking current | kA | 25, 31.5 |
4 | Dynamic current (peak) | 63, 80 | |
5 | 4s thermal stability current | 25, 31.5 | |
6 | Rated short circuit making current (peak) | 63, 80 | |
7 | Rated short circuit current breaking number | Times | 20 |
8 | Rated operating sequence | O-0.3s-CO-180s-CO | |
9 | 1 min power frequency withstand voltage | kV | 95 |
10 | Rated lightning impulse withstand voltage | 185 | |
11 | Mechanical life | Times | 10000 |
12 | Rated single capacitor bank switching current | A | 630 |
13 | Rated back-to-back capacitor bank current | 400 | |
14 | Rated voltage of energy storage motor | IN | AC/DC 220/110 |
15 | Power of energy storage motor | IN | ≤230 |
16 | Energy storage time | s | ≤15 |
17 | Ratea voltage of closing/opening coil | IN | DC 220/110 |
18 | Rated current of closing/opening coil | A | 1.05(110V) 0.96(220V) |
19 | Clearance between open contacts | mm | 20±2 |
20 | Contact travel | 7.5±1.5 | |
twenty one | Three phase opening and closing asynchronism | ms | ≤2 |
twenty two | Contact closing bounce time | ≤3 | |
twenty three | Main circuit resistance (not include contact arm) | mΩ | ≤40 |
General Structure Drawing and Installation Size (unit: mm)
♦ Draw out type assembled pole
♦ Draw out type embedded pole