ZN12-12/40.5 Series Indoor High Voltage Vacuum Circuit Breaker

Short Description:


Product Detail

Product Tags

ZN12-12/40.5 indoor HV vacuum circuit breaker is a 3-phase AC 50Hz 12kV/40.5KV indoor switch equipment.

♦ Installation way: withdrawable type, fixed type;

♦ Operating mechanism: spring ope rating mechanism;

♦ Application: switchgear GBC-35, JYN1-35.

 

Environmental Conditions

♦ Ambient temperature: -25°C~+40°C;

♦ Altitude:

♦ Relative humidity: daily average ;

♦ Earthquake intensity:

♦ Places without fire, explosion hazard, serious filthy, chemical corrosion, as well as intense vibration.

 

Main Technical Parameters

ZN12-12

No Item

Unit

Value

1 Rated voltage

kV

2 Rated current

A

630, 1250, 1600

1250, 1600,2000,

2500,3150

2000, 2500,

3150,4000

3 Rated short circuit breaking current

kA

20

25

31.5

40

50

4 Dynamic stability current (peak)

kA

50

63

80

100

125

5 4s thermal stability current

kA

20

25

31.5

40/3s

50/3s

6 Rated short circuit making current

kA

50

63

80

100

125

7 Short circuit current breaking number times

30

12

8 Rated operating sequence

CO-0.3S-CO-180S-CO

O-180S-CO-180S-CO

9 Mechanical life times

10000

6000

10 Rated current breaking number times

10000

6000

11 Rated lightning impulse withstand voltage (full wave)

kV

75

12 Rated short time power frequency withstand current (1 min)

kV

42

13 Closing time

ms

≤75

14 Opening time

ms

≤65

15 Power and rated voltage of energy storage motor

W/V

275W/ 110V, 220V

16 Energy storage time

s

 

No

Item

Unit

Value

17 Rated voltage of closing coil

IN

110V, 220V

18 Rated voltage of opening coil

IN

19 Rated voltage of interlock coil

IN

20 Rated current of release

A

5

twenty one Rated current of auxiliary switch

A

AC10A, DC5A

ZN12-40.5

No Item

Unit

Value

1 Rated voltage

kV

40.5

2 Rated current

A

1250, 1600,

2000

1250, 1600,2000,2500
3 Rated short circuit breaking current

kA

20, 25

31.5
4 Dynamic stability current (peak)

kA

50, 63

80
5 4s thermal stability current

kA

20, 25

31.5
6 Rated short circuit making current (peak)

kA

50, 63

80
7 Short circuit current breaking number times

30

20
8 Rated operating sequence

CO-0.3S-CO-180S-CO

9 Rated lightning impulse withstand voltage (full wave)

kV

180

10 Rated short time power frequency withstand current (1 min)

kV

95

11

Closing time

ms

≤90

12 Opening time

ms

≤75

13 Mechanica! life times

10000

60000
14 Rated current breaking number times

10000

60000
15 Rated capacitor bank breaking current

A

630

Power of energy storage motor

IN

275

17 Rated voltage of energy storage motor

IN

≃110V, 220V

18

Energy storage time

s

≤15

19

Rated voltage of closing and opening coil

IN

≃110V, 220V

20

Rated current of overcurrent release

A

5

twenty one

Rated current of auxiliary switch

A

AC10A, DC5A

 

General Structure Drawing and Installation Size (unit: mm)

ZN12-12 (inclined mounted)

rht (1)

Note: dimension 360mm is for current above 2000A, under 2000A, the dimension is 350mm.

rht (2)

Note, in the figure, (215) means when L3=516mm, the dimension is 215mm.

Under 1600A: upper and lower outlet terminal hole 2-M12

Above 2000A: upper and lower outlet terminal hole 4-M12

Type

L

L1

L2

L3

Remarks

ZN12-12

210

586

610

516

With inter-phase partition

230

620

650

565

250

700

740

565

275

696

720

516

ZN12-12B (flush mounted)(569575)

svd

Note: (575) and (364) mean when short circuit breaking current is 40kA or above, the dimensions are 575mm, 364mm.

is

Upper and lower outlet terminal hole 4-M12

Note: (215) means when L3=516mm; the dimension is 215mm.

Type

L

L1

L2

L3

ZN12-12B

210

586

610

516

230

620

650

565

250

700

740

565

275

696

720

516

Remarks With inter-phase partition


  • Previous: