JB 12/24KV-630A European Style Touchable Detachable Front Joint

Short Description:


Product Detail

Product Tags

Application

* Connect single-phase or three-phase insulated cables to transformers, switchgears, branch boxes and other equipment through 630A prefabricated connectors.

* Suitable for indoor and outdoor installation.

* Rated voltage: 8.7/15kV, 18/24kV

* Continuous rated current 630A; (900A overload can last for 8 hours)

* Extendable (JBK) rear connector or (HBLQ) series surge arrester to achieve multi-channel installation or provide overvoltage protection.

* Cable characteristics:

-Copper or aluminum conductor

-Has semi-conductive or metal shield

-Cable conductor cross section: 12kV 25-500mm2, 24kV 25-500mm2

Type Description

rhtr

Feature

* When mated with a suitable bushing or plug, it provides a fully shielded and fully sealed detachable connection;

* Can be operated under water and other harsh conditions for a long time;

* The built-in capacitance test point is used to determine the charged state of the circuit, and must be used in conjunction with the charged display;

* No requirements for minimum safety distance between phases;

* The installation can be vertical, horizontal or any angle

Product Structure

1. Double-headed bolts: Metal bolts ensure that the conductor and the bushing are tightly matched.

2. Insulation layer: unique formula and mixing technology ensure the high quality of prefabricated insulating silicone rubber.

3. Insulator: The epoxy resin insulator contains threaded metal parts to ensure a close fit with the stud bolts.

4. Inner semiconducting layer: Prefabricated conductive silicone rubber effectively controls electrical stress.

5. Stress cone: Stress cones of different sizes are used with cable joints to ensure water sealing and cable stress relief.

6. Grounding eye: pre-injected into the outer shield for the connection of the grounding wire.

7. Outer semiconducting layer: The prefabricated conductive rubber overlaps with the cable shielding layer to make the shielding continuous and ensure that the outer semiconducting layer is grounded.

8. Crimping terminal: All-copper or copper-aluminum crimping terminal is suitable for copper or aluminum conductor.

bf

Installation

* No special tools, straps or padding required;

* The cable connector is energized and operated immediately after being installed to the relevant parts;

* Provide regular assembly parts and installation manual.

* (Please contact our company for special requirements)

 

Standard Packaging

European style front joint body utility knife
stress cone band Aid
insulator cleaning paper
dust cap silicone grease
crimp terminal (copper or copper aluminum) gloves (white, yellow)
gloves (disposable)
socket wrench sealant (red)
M16/12 double-head screw nylon cable tie (buckle)
M12 nut, flat washer, spring washer PVC electrical tape (red yellow, green)
tape certificate of quality
sandpaper installation instruction manual

12KV Cable Type Configuration Table

Product model

Conductor cross section (mm2)

Cable insulation outer

diameter (mm)

Cable type

Corresponding code

JB-12/630-25

25

16.6

8.7/15

0

JB-12/630-35

35

17.6

8.7/15

A

JB-12/630-50

50

19

8.7/15

A

JB-12/630-70

70

20.6

8.7/15

A

JB-12/630-95

95

22.2

8.7/15

B

JB-12/630-120

120

23.6

8.7/15

B

JB-12/630-50

150

25.5

8.7/15

C

JB-12/630-185

185

26.7

8.7/15

C

JB-12/630-240

240

29

8.7/15

D

JB-12/630-300

300

31.2

8.7/15

D

JB-12/630-400

400

34.4

8.7/15

AND

JB-12/630-500

500

37.2

8.7/15

F

24KV Cable Type Configuration Table

Product model Conductor cross section (mm2)

Cable insulation outer

diameter (mm)

Cable type

Corresponding code

JB-24/630-35

35

18.6

18/20

B

JB-24/630-50

50

19.6

18/20

B

JB-24/630-70

70

twenty one

18/20

B

JB-24/630-95

95

22.6

18/20

C

JB-24/630-120

120

24.2

18/20

C

JB-24/630-150

150

25.6

18/20

D

JB-24/630-185

185

27.2

18/20

D

JB-24/630-240

240

28.7

18/20

AND

JB-24/630-300

300

311.

18/20

AND

JB-24/630-400

400

33.2

18/20

F

Note: The outer diameter of the cable is the decisive factor when selecting the model, and the conductor cross section is the reference.