General
Busbar system can be used between 12kV GIS switchgear systems, busbar connection for a minimum center distance of 280mm, suitable for the maximum current 630A, 1250A. The above busbar system uses a bolt crimping structure, and the flexible connection is not sensitive to the height error of the splicing cabinet.
The busbar is combined with the 630A +-connector and T-connector. It is installed on the socket of the switch and can realize the series connection of multiple load switches. It is the preferred solution for the combined ring main unit.
European-style +-connector and T-connector can be arbitrarily customized according to customer requirements.
Note: the length can be customized according to customer requirements.
Voltage: 8.7/15kV, 18/24kV
Model: 8.7/15kV~630A(1250A), 18/24kV~630A(1250A)
Features: Used for busbar connection between switchgears, current 630A.
Product Structure
1. 630A/1250A equipment bushing
2. M16/12 double-head reducing screw
3. terminal fitting
4. metal balance pad
5. flat washer
6. spring washer
7. M12 nut
8. insulation plug
9. back cover (black)
10. copper busbar holder T-connector
11. shielding busbar
12. -connector
13. earthing
14. sealant
Ordering Information
Shielding busbar: The processing length L is based on the center distance between the bushings of the two switchgears, and parameters must be provided when ordering; if the busbar length is used as the basis, please specify.
product name | product model |
12KV European Style Touchable Detachable Busbar | MX 12kV-630A |
MX 12kV-1250A | |
24KV European Style Touchable Detachable Busbar | MX 24kV-630A |
MX 24kV-1250A |
Switchgear connection | T- connector | +-connector | Brsbar (according to the center distance) |
two cabinets | 2 sets | / | Iset |
three cabinets | 2 sets | Iset | 2sets |
four cabinets | 2 sets | 2sets | 3 sets |
five cabinets | 2 sets | 3 sets | 4sets |
six cabinets | 2 sets | 4sets | 5 sets |
n cabinets | 2 sets | (n-2) sets | (n-1) sets |