VSG-12 Series Indoor High Voltage Vacuum Circuit Breaker

Short Description:


Product Detail

Product Tags

VSG-12 indoor HV vacuum circuit breaker is a 3-phase AC 50Hz 12kV indoor switch equipment.

♦ Installation way: withdrawable type, fixed type;

♦ Operating mechanism: spring operating mechanism;

♦ Pole type: assembled pole, embedded pole;

♦ Phase-to-phase distance: 150mm, 210mm, 275mm;

Environmental Conditions

♦ Ambient temperature: -15r~+40r;

♦ Altitude:

♦ Relative humidity: daily average ;

♦ Earthquake intensity:

♦ Places without fire, explosion hazard, serious filthy, chemical corrosion, as well as intense vibration.

Main Technical Parameters

No

Item

Unit

Value

1 Rated voltage

kV

12

2 1 min power frequency withstand voltage

42

3 Rated lightning impulse withstand voltage

75

4 Rated frequency

Hz

50

5 Rated current A

630, 1250, 1600, 2000, 2500,

3150

6 Rated short circuit breaking current

kA

25, 31.5, 40

7 Rated short time withstand current

25, 31.5, 40

8 Rated short circuit duration s

4

9 Rated peak value withstand current

kA

63, 80, 100

10 Rated short circuit making current

63, 80, 100

11 Secondary circuit power frequency withstand voltage (Imin) IN

2000

12 Rated single / back-to-back capacitor bank breaking current A

630/400 (800/400 for 40kA)

Opening time (rated voltage)

ms

20-50

14

Closing time (rated voltage)

ms

35-70

15

Mechanical life

Times

10000

16

Electrical life

E2 class

17

Moving and fixed contacts cumulative allowed wear thickness mm

3

18

Rated closing operating voltage IN

AC/DC110/220

19

Rated opening operating voltage

 

No

Item

Unit

Value

20

Motor rated power

IN

90

twenty one

Charging time

s

≤15

twenty two

Clearance between open contacts

mm

9±1

twenty three

Over travel

mm

3±1

twenty four Contact closing bounce time

ms

≤2

25

Three phase opening and closing asynchronism

ms

≤2

26 Average opening speed

m/s

0.9-1.7

27 Average closing speed

m/s

0.6~1.0

28

Main conductive circuit resistance

≤45 (630A) ≤35(1250-2000A)

≤25(above 2500A)

29 Closing contact pressure of the contacts N

3100-3700 (25-31.5kA)

4400-4800 (40kA)

30 Rated operating sequence

O-0.3s-CO-180s-CO

Note: when current is 4000A, need forced air cooling.

General Structure Drawing and Installation Size (unit: mm)

Draw out type (assembled pole)

w1

cabinet width

rated current (A)

rated short circuit breaking current (kA)

P H A

B

C

D

AND

F

G

J

K

L

M

N

R

S

T

650

630

20'31.5

150 275 490 502 492 500 433 626 035 280 598 76 78 637 501 202 40
650 12j0

20-31.5

150 275 490 502 492 500 433 626 049 280 598 76 78 637 501 202 40

800

630

20-31.5

210 275 638 652 640 650 433 626 035 280 598 76 78 637 501 277 40
800 1250

20-40

210 275 638 652 640 650 433 626 049 280 598 76 78 637 501 277 40
800 1600

31.5-40

210 275 638 652 640 650 433 626 055 280 598 76 78 637 501 277 40
WOO 030

20-31.5

275 275 838 852 838 850 433 626 035 280 598 76 78 637 501 377 40
1000 1250

20-40

275 275 838 852 838 850 433 626 049 280 598 76 78 637 501 377 40
1000 1600

31.5-40

275 275 838 852 838 850 433 626 055 280 598 76 78 637 501 377 40
1000 1600-2000

31.5-40

310 310 838 852 838 850 361 680 079 295 586 77 88 698 529 377

0

1000 2500-4000

31.5-40

310 310 838 852 838 850 361 680

0109

295 586 77 88 698 529 377 0

♦ Draw out type (embedded pole)

w2

G

J

K

L

M

N

R

S

T

0)35 280 598

76

78

637 501

202

40
①49 280 598

76

78

637 501

202

40
035 280 598

76

78

637 501

277

40
①49 280 598

76

78

637 501

277

40
(D79 295 586

77

88

698 509

377

0

0109 295 586

77

88

698 509

377

0

Fixed type (assembled pole)

w3

A

B

C

AND

F

G1 G2

J

K

520

520

588

580

72

I

237

462

720

720

770

580

72

I

237

462

650

720

770

632

85

II

252

472

♦ Fixed type (embedded pole)

q1 q2


  • Previous: