VSG-24 indoor HV vacuum circuit breaker is a 3- phase AC 50Hz 24kV indoor switch equipment
♦ Operating mechanism: spring operating mechanism;
♦ Pole type: assembled pole: embedded pole;
♦ phase-to-phase distance: 275mm;
Environmental Conditions
♦ Ambient temperature:-15°C ~+40°C;
♦ Altitude:
♦ Relative humidity: daily average ;
♦ Earthquake intensity:
♦ Places without fire, explosion hazard, serious filthy, chemical corrosion, as well as intense vibration.
Main Technical Parameters
No | Item | Unit | Value |
1 | Rated voltage | kV | twenty four |
2 | 1 min power frequency withstand voltage | 65 | |
3 | Rated lightning impulse withstand voltage | 125 | |
4 | Rated frequency | Hz | 50/60 |
5 | Rated current | / | 630, 1250, 1600, 2000, 2500,3150 |
6 | Rated short circuit breaking current | kA | 25, 31.5 |
7 | Rated short circuit making current (peak) | 63, 80 | |
8 | Rated short time withstand current | 25, 31.5 | |
9 | Rated peak value withstand current | 63, 80 | |
10 | Rated short circuit duration | S | 4 |
11 | Rated operating sequence | O-0.3s-CO-180s-CO | |
12 | Secondary circuit power frequency withstand voltage (1min) | IN | 2000 |
13 | Rated single/back-to-back capacitor bank breaking current | kA | 630 |
14 | Breaking time | ms | 20~50 |
1; | Opening time | 35-70 | |
16 | Mechanical life | times | 10000 |
17 | Electrical life | E2 class | |
18 | Power of energy storage motor | IN | 90 |
19 | Control circuit power supply voltage | IN | AC/DC110/220 |
General Structure Drawing and Installation Size (unit: mm)
♦Draw out type
Rated current (A) | 630 | 1250 | 1600 |
Rated short circuit breaking current (kA) | 25, 31.5 | 25, 31.5 | 31.5 |
Fixed contact size (mm) | 035 | 049 | 055 |
Phase-to-phase distance (mm) | 275 |